ESP 415T1 Surge Protection Series are a Combined Type 1 and 2 tested protector (to BS EN 61643) for use on the main distribution board, particularly where a structural Lightning Protection System (LPS) is employed, for equipotential bonding. For use at boundaries up to LPZ 0 to protect against flashover (typically the main distribution board location) through to LPZ 2 to protect electrical equipment from damage.

Nominal Voltage - Phase-Neutral Uo (RMS): 240 V
Maximum Voltage - Phase-Neutral Uc (RMS): 415T1/25-275V, 415T1/12.5-300V
Temporary Over-voltage TOV UT (1): 337 V / 442 V
Short Circuit Withstand Capability: 50Ka / 50Hz
Frequency Range: 47-63 Hz
Max. Back-up Fuse: 415T1/25 315A, 415T1/12.5 250A
Leakage Current (to earth): 415T1/25 5µA, 415T1/12.5 600µA
Volt Free Contact: Push-fit connection for conductor up t0 1.5mm2, rated AC 250V, 1A
Temperature Range: -40°C to + 80°C
Connection Type: Screw Terminal
Conductor Size (solid/stranded): 35mm²
Earth Connection: Screw Terminal
Protection: IP20

See Downloads Tab for full Datasheet

Swipe table
Code For Use With Transient Spec Type 1(BS EN/EN), Class I(IEC)Nom discharge current 8/20 up(per mode)/n Impulse discharge current 10/350us/imp Let-through voltage up at /imp² Nom discharge current 8/20 up (per mode)In Max discharge current /max(per mode)3 Enclosure Exc. VAT Inc. VAT
ESP415T1/25/TNS Class I or II LPS 25kA 25kA < 1.5kV 25kA 65kA WBXD4 £1,001.32 £1,201.58
ESP415T1/12.5/TNS Class III or IV LPS 20kA 12.5kA < 1.5kV 20kA 50kA WBXD4 £622.62 £747.14
ESP415T1/25/TNC Class I or II LPS 25kA 25kA < 1.5kV 25kA 65kA WBXD4 £731.64 £877.97
ESP415T1/12.5/TNC Class III or IV LPS 20kA 12.5kA < 1.5kV 20kA 50kA WBXD4 £521.24 £625.49